Transformer Sizing Calculator

Size transformers based on connected load and demand factors.

Recommended: 20-25% for future expansion

Transformer Sizing Formulas

kVA from kW:

kVA = kW / Power Factor

Three-Phase kVA:

kVA = (V x I x 1.732) / 1000

Single-Phase kVA:

kVA = (V x I) / 1000

Transformer Requirements (NEC Article 450)

Primary Protection

Transformers over 1000V: 125% for fuses, 300% for circuit breakers. Under 1000V with primary protection only: 125%.

Secondary Protection

Secondary conductors sized at 125% of secondary FLA. OCPD sized per 240.4 based on conductor ampacity.

Ventilation

Dry-type transformers require adequate ventilation. Liquid-filled must meet NEC 450.27 vault requirements.