NEC Quick Reference Tables

NEC Table 310.16 - Ampacity of Insulated Conductors

Based on 30°C (86°F) ambient, 3 current-carrying conductors in raceway or cable

Wire Size Copper Aluminum
60°C 75°C 90°C 60°C 75°C 90°C
#14152025---
#12202530152025
#10303540253035
#8405055354045
#6556575405055
#4708595556575
#385100115657585
#2951151307590100
#111013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250215255290170205230
300240285320195230260
350260310350210250280
400280335380225270305
500320380430260310350
Note: For ambient temperatures other than 30°C (86°F), apply correction factors per NEC 310.15(B)(1).

Temperature Correction Factors

Multiply ampacity by these factors for ambient temperatures other than 30°C

Ambient °C Ambient °F 60°C 75°C 90°C
21-2570-771.081.051.04
26-3078-861.001.001.00
31-3587-950.910.940.96
36-4096-1040.820.880.91
41-45105-1130.710.820.87
46-50114-1220.580.750.82
51-55123-1310.410.670.76

Conduit Fill Adjustment Factors

Derate ampacity when more than 3 current-carrying conductors in raceway

Current-Carrying Conductors Percent of Table Value
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%

Conduit Fill - NEC Chapter 9, Table 1

Number of Conductors Percent Fill Allowed
153%
231%
3 or more40%

EMT Internal Area (sq in)

Trade Size Total Area 1 Wire (53%) 2 Wires (31%) 3+ Wires (40%)
1/2"0.3040.1610.0940.122
3/4"0.5330.2820.1650.213
1"0.8640.4580.2680.346
1-1/4"1.4960.7930.4640.598
1-1/2"2.0361.0790.6310.814
2"3.3561.7791.0401.342
2-1/2"5.8583.1051.8162.343
3"8.8464.6882.7423.538
4"14.7537.8194.5735.901

THHN/THWN Wire Area (sq in)

Wire Size Area (sq in) Wire Size Area (sq in)
#140.0097#10.1562
#120.01331/00.1855
#100.02112/00.2223
#80.03663/00.2679
#60.05074/00.3237
#40.08242500.3970
#30.09733000.4608
#20.11583500.5242

Box Fill - NEC 314.16

Volume Allowances per Conductor

Wire Size Volume (cu in)
#181.50
#161.75
#142.00
#122.25
#102.50
#83.00
#65.00

Standard Box Volumes

Box Type Volume (cu in)
4 × 1-1/4 Square18.0
4 × 1-1/2 Square21.0
4 × 2-1/8 Square30.3
4-11/16 × 1-1/4 Square25.5
4-11/16 × 1-1/2 Square29.5
4-11/16 × 2-1/8 Square42.0
3 × 2 × 2 Device7.5
3 × 2 × 2-1/4 Device10.0
3 × 2 × 2-1/2 Device10.5
3 × 2 × 2-3/4 Device12.5
3 × 2 × 3-1/2 Device18.0
Box Fill Rules:
  • Each conductor = 1× volume
  • All internal clamps = 1× largest conductor
  • Each support fitting = 1× largest conductor
  • Each device/yoke = 2× largest conductor
  • All equipment grounds = 1× largest conductor

Motor Full Load Amps - NEC Tables 430.248, 430.250

Single-Phase AC Motors (Table 430.248)

HP 115V 200V 208V 230V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.14.03.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1-1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7-1/280464440
1010057.55550

Three-Phase AC Motors (Table 430.250)

HP 208V 230V 460V 575V
1/22.42.21.10.9
3/43.53.21.61.3
14.64.22.11.7
1-1/26.66.03.02.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
7-1/224.222119
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552

Overcurrent Protection Quick Reference

Standard Breaker Sizes (NEC 240.6)

Standard ampere ratings for fuses and inverse time circuit breakers

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000

Branch Circuit Wire/Breaker Combinations

Breaker Size Min Wire (Cu) Min Wire (Al) Common Uses
15A#14#12Lighting, general receptacles
20A#12#10Kitchen, bathroom, garage receptacles
30A#10#8Dryer, water heater, small A/C
40A#8#6Range (small), large A/C
50A#6#4Range, EV charger, subpanel
60A#6#4Subpanel, large A/C
100A#3#1Subpanel, service
200A2/04/0Main service

Motor Branch Circuit Protection (430.52)

Motor Type Time Delay Fuse Inverse Time Breaker Instant Trip Breaker
Single-phase175%250%800%
AC polyphase (other than wound-rotor)175%250%800%
Wound-rotor150%150%800%
DC150%150%250%

If the calculated value doesn't match a standard size, round up to the next standard size per 430.52(C)(1) Exception 1.