Wire Sizing Calculator

Find the correct wire gauge for ampacity and voltage drop per NEC requirements.

Distance from panel to load

Quick Reference

Circuit Typical Wire Breaker
15A Branch#14 Cu15A
20A Branch#12 Cu20A
30A Circuit#10 Cu30A
40A Circuit#8 Cu40A
50A Circuit#6 Cu50A
60A Feeder#6 Cu60A
100A Service#3 Cu100A
200A Service#2/0 Cu200A

*Based on 75°C copper, short runs. Always verify with full calculation for long runs.

Understanding Wire Sizing

Two Critical Factors

Wire sizing must satisfy two requirements:

  1. Ampacity - The wire must safely carry the load current without overheating (NEC 310.16)
  2. Voltage Drop - The wire must deliver adequate voltage to the load (NEC recommends max 3% for branch circuits, 5% total)

Derating Factors

Ampacity must be derated for:

  • Temperature - Higher ambient temps reduce ampacity
  • Conduit Fill - More than 3 current-carrying conductors reduces ampacity
  • Continuous Loads - Loads operating 3+ hours require 125% sizing

Voltage Drop Formula

Single Phase: VD = (2 × L × I × R) / 1000

Three Phase: VD = (1.732 × L × I × R) / 1000

Where: L = one-way length (ft), I = current (A), R = resistance (Ω/1000ft)