Switchgear Rating Calculator
Determine switchgear ratings and verify interrupting capacity per NEC 110.9.
Standard AIC Ratings
| Equipment | Typical AIC (kA) |
|---|---|
| Residential Panel | 10 - 22 kA |
| Commercial MCCB | 14 - 65 kA |
| Industrial MCCB | 25 - 100 kA |
| ICCB | 42 - 100 kA |
| LVPCB (Draw-out) | 65 - 200 kA |
| MV Switchgear | 20 - 63 kA |
Typical Frame Sizes (480V MCCB)
| Frame | Max Amps | AIC Options |
|---|---|---|
| 100A | 100A | 14-65 kA |
| 250A | 250A | 22-65 kA |
| 400A | 400A | 25-100 kA |
| 800A | 800A | 42-100 kA |
| 1600A | 1600A | 42-100 kA |
| 2500A | 2500A | 65-100 kA |
NEC Requirements for Switchgear
NEC 110.9 - Interrupting Rating
- Equipment must have interrupting rating sufficient for available fault current
- Series ratings allowed per NEC 240.86
- Must be marked with AIC rating
- Consider motor contribution to fault
NEC 110.10 - Circuit Impedance
- Equipment must withstand fault current without damage
- Verify short-circuit current rating (SCCR)
- Consider component damage threshold
- Coordinate with upstream protection