Short Circuit Current Calculator
Calculate available fault current at downstream equipment.
Short Circuit Formulas
Three-Phase SCC at Transformer:
Isc = (kVA x 1000) / (V x 1.732 x %Z/100)
Simplified Point-to-Point:
Isc2 = Isc1 / (1 + (f x L / C))
f = factor based on voltage, L = length (ft), C = conductor constant
NEC Requirements for Short Circuit Ratings
NEC 110.9
Equipment intended to interrupt current must have an interrupting rating not less than the nominal circuit voltage and current to be interrupted.
NEC 110.10
Equipment must be selected and coordinated to clear a fault without extensive damage to the electrical equipment.
NEC 409.110
Industrial control panels must be marked with short-circuit current rating and the protection must not exceed this rating.
Important: Equipment AIC ratings must equal or exceed available fault current. Series-rated systems may allow lower-rated downstream equipment when properly coordinated.