Service Entrance Sizing

Size service conductors and equipment per NEC 230

Service Requirements

Minimum Conductor Size --
Service Conductors --
Neutral Size --
Grounding Electrode Conductor --
Minimum Conduit Size --
Main Breaker --
Meter Base --

NEC References

• Service conductors: NEC 230.42

• Neutral sizing: NEC 220.61

• GEC sizing: NEC 250.66, Table 250.66

• Grounding: NEC 250.24

Service Conductor Sizing Reference

Service (A) Copper 75°C Aluminum 75°C GEC (Cu) GEC (Al)
1004 AWG2 AWG8 AWG6 AWG
1252 AWG1/0 AWG8 AWG6 AWG
1501 AWG2/0 AWG6 AWG4 AWG
2002/0 AWG4/0 AWG4 AWG2 AWG
400400 kcmil600 kcmil1/0 AWG3/0 AWG
6002×3/02×2502/0 AWG4/0 AWG
8002×2502×4003/0 AWG250 kcmil