Motor Full Load Amperage Tables

NEC Tables 430.248, 430.249, and 430.250

Table 430.248 - Single-Phase AC Motors

HP 115V 200V 208V 230V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.14.03.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1-1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7-1/280464440
1010057.55550

Table 430.250 - Three-Phase AC Motors

HP 208V 230V 460V 575V
1/22.42.21.10.9
3/43.53.21.61.3
14.64.22.11.7
1-1/26.66.03.02.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
7-1/224.222119
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552
601691547762
752111929677
10027324812499
125343312156125
150396360180144
200528480240192

Table 430.247 - DC Motors

HP 120V 240V
1/43.11.6
1/34.12.0
1/25.42.7
3/47.63.8
19.54.7
1-1/213.26.6
2178.5
32512.2
54020
7-1/25829
107638

Motor Circuit Sizing Rules

Conductor Sizing (430.22)

• Single motor: FLA × 125%

• Multiple motors: Sum of FLA + 25% of largest

Overcurrent Protection (430.52)

• Inverse time breaker: FLA × 250%

• Dual element fuse: FLA × 175%

Note: Always use nameplate FLA when available. These tables are for circuit sizing when nameplate data is not available.