Lighting Power Density Calculator

Calculate LPD for energy code compliance per ASHRAE 90.1.

Total connected lighting load

LPD Allowances (ASHRAE 90.1-2022)

Space Type W/sq ft
Open Plan Office0.72
Enclosed Office0.74
Conference Room0.97
Corridor0.41
Retail Sales1.05
Classroom0.71
Warehouse (Bulk)0.33

Building Area Method LPD Allowances

Building Type ASHRAE 90.1-2022 ASHRAE 90.1-2019 Notes
Office0.64 W/sf0.79 W/sfMost common application
Retail0.84 W/sf1.06 W/sfIncludes display lighting
Warehouse0.45 W/sf0.48 W/sfGeneral storage areas
School0.72 W/sf0.81 W/sfK-12 and higher ed
Hospital0.96 W/sf1.05 W/sfInpatient facilities
Hotel0.56 W/sf0.75 W/sfGuest rooms and common
Restaurant0.71 W/sf0.90 W/sfDining areas
Manufacturing0.82 W/sf0.95 W/sfProduction areas