Lighting Layout Calculator
Calculate number of fixtures needed using the lumen method (zonal cavity).
Lumen Method Formula
Number of Fixtures:
N = (FC x Area) / (Lumens x CU x LLF)
Room Cavity Ratio:
RCR = 5h x (L + W) / (L x W)
IES Recommended Lighting Levels
| Space Type | Foot-Candles | Lux | Notes |
|---|---|---|---|
| Corridors/Hallways | 5-10 | 50-100 | Basic circulation areas |
| Storage/Warehouse | 10-30 | 100-300 | Inactive storage |
| General Office | 30-50 | 300-500 | Computer work, reading |
| Classroom | 50-75 | 500-750 | Reading and writing tasks |
| Retail/Showroom | 50-100 | 500-1000 | Merchandise display |
| Detailed Work | 75-100 | 750-1000 | Drafting, accounting |
| Manufacturing | 50-100 | 500-1000 | General assembly |
| Fine Assembly/Inspection | 100-200 | 1000-2000 | Electronics, quality control |