Lighting Layout Calculator

Calculate number of fixtures needed using the lumen method (zonal cavity).

Floor to luminaire
Typically 2.5 ft (desk height)
Typical: 0.5-0.8
Typical: 0.7-0.9

Lumen Method Formula

Number of Fixtures:

N = (FC x Area) / (Lumens x CU x LLF)

Room Cavity Ratio:

RCR = 5h x (L + W) / (L x W)

IES Recommended Lighting Levels

Space Type Foot-Candles Lux Notes
Corridors/Hallways5-1050-100Basic circulation areas
Storage/Warehouse10-30100-300Inactive storage
General Office30-50300-500Computer work, reading
Classroom50-75500-750Reading and writing tasks
Retail/Showroom50-100500-1000Merchandise display
Detailed Work75-100750-1000Drafting, accounting
Manufacturing50-100500-1000General assembly
Fine Assembly/Inspection100-2001000-2000Electronics, quality control