Grounding Grid Design
Calculate grid parameters per IEEE Std 80-2013.
Typical Soil Resistivity Values
| Soil Type | Resistivity (ohm-m) |
|---|---|
| Sea water | 0.1 - 1 |
| Clay, wet | 5 - 20 |
| Loam, moist | 20 - 100 |
| Sand, wet | 50 - 200 |
| Sand, dry | 200 - 3000 |
| Gravel | 300 - 5000 |
| Rock | 1000 - 100000 |
IEEE 80 Design Principles
Tolerable Voltages (50kg person)
E_touch = (1000 + 1.5 × Cs × ρs) × 0.116 / √ts
E_step = (1000 + 6 × Cs × ρs) × 0.116 / √ts
Design Criteria
- E_touch (calc) ≤ E_touch (tolerable)
- E_step (calc) ≤ E_step (tolerable)
- Conductor must withstand fault current
- Surface layer reduces body current
- Ground rods reduce resistance