Emergency Generator Sizing

Size standby generators including motor starting and step loading.

Running Loads

Motor Starting Loads

System Configuration

Standard generators rated at 0.8 PF

NEC Article 700 Requirements

  • Generator must start and assume load within 10 seconds (700.12)
  • Fuel supply for Class 1 Level 1: 2 hours minimum
  • Monthly testing required under load (700.3)
  • Transfer equipment must prevent interconnection (700.5)
  • Emergency circuits must be kept separate from normal circuits

Generator Sizing Considerations

Motor Starting

Motors draw 3-8x FLA during starting. Size generator for peak starting current plus running loads.

Step Loading

Maximum step load typically 1/3 of generator rating. Sequence loads for best performance.

Power Factor

Generators rated at 0.8 PF. kVA = kW / PF. Low PF loads reduce real power capacity.

Tip: Add 20-25% safety factor for future expansion and non-linear loads. Consider harmonics from VFDs and UPS systems.