Cable Ampacity Derating

Calculate derated ampacity based on NEC 310.15 correction factors.

Derating Factors

NEC 110.14(C) - Use lower of conductor or terminal rating

NEC 310.15 Derating

Final ampacity = Base x Temp Factor x Fill Factor

For continuous loads, conductor must be sized for 125% of load (or use 80% of ampacity).

NEC 310.15(B)(1) - Conduit Fill Adjustment Factors

Conductors in Raceway Adjustment Factor
1-3100%
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%
Note: Only current-carrying conductors count. Equipment grounding and neutral conductors (under certain conditions) may not count.